Every case below is from Gasonic's own field work. They are why we built a framework that goes beyond the code minimum.
Banff, Alberta · November 2022
CO in the bedroom above the garage
We were called to service a parkade CO system. It was working to the manufacturer's specification, but that specification was set for maximum energy savings, so the fans shut off while exhaust was still in the air.
We left data loggers in the garage and in the suite directly above. When our technician returned, a girl was home sick with flu-like symptoms, an early sign of CO exposure, sleeping in the bedroom where the logger had been placed. Unsealed water pipes in the kitchen and bathroom had let garage air into the unit.
Garage below bedroom · CO ppm, 24 hBedroom above garage · CO ppm, 24 h
Ventilation did not run long enough to clear the air from the 8 am rush until 2 pm. A detailed review of the logs found more than 500 ppm in the garage at its worst, well above the OHS ceiling of 125 ppm.
Calgary · March 2001
Fans disconnected to save energy
A worker pressure-washing a downtown parkade collapsed. Ten people went to hospital and he was flown to Edmonton for hyperbaric treatment. He recovered. Our investigation found the control wires to the exhaust fans had been cut, because the fans "ran too long."
Alberta has had CO incidents in parkades nearly every year since, often during spring cleaning.
Why it matters for owners
Workers are protected by law. Residents often are not.
Air quality complaints from workers must be investigated under occupational health and safety rules. A family raising the same concern about their suite has no such guarantee. Protecting occupants is also how owners and property managers protect themselves from liability.